Quick answerA fire door hinge must match the door's certificate: the same size, material, pin type and screw hole pattern, with a CE or UKCA mark and a declared fire performance, usually to BS EN 1935. Reuse the existing screw holes. Do not drill new ones, and let the certificate and a qualified installer decide if anything does not match.

Replacing a hinge on a fire door is not the same as swapping a hinge on an internal door. The hinge is part of the tested door assembly, and the certificate names the hardware that was assessed with the leaf. This guide is for installers, maintenance teams and building managers who need to check a hinge before ordering a replacement. The certificate and the competent person on site decide.

What makes a hinge suitable for a fire door?

A fire door is tested as a complete assembly: leaf, frame, seals, hinges, closer, lock and handles. The hinge is not an accessory that can be swapped for any hinge of the same size. It has a declared fire performance as part of that assembly, and the door's certificate records the product or the specification that was tested.

Fire door hinges are usually single-axis butt hinges in steel or stainless steel, with a fixed pin. A fixed pin is held in the knuckle and cannot be lifted out, which suits a door that has to stay in place. Ball bearings reduce friction and help the door swing freely, but the bearings are not what makes the hinge fire rated.

The hinge also has to carry the door. A fire door leaf is often solid and heavy, and a closer pulls on it every time it shuts. A thin hinge from a general hardware range may fit the screw holes and still not suit the door's weight or its tested configuration.

Smoke seals and intumescent strips are separate parts of the assembly, but they are close to the hinge line. A hinge that is the wrong size can pinch a seal, and a door that drops can tear one. Check them before and after the swap, even though they are not part of the hinge itself.

What does the door certificate tell you about hinges?

The certificate, test evidence or hardware schedule is the starting point. It should identify the door assembly and the hardware that goes with it. On a modern certificated door, the schedule may list a specific hinge product, or a specification with a minimum performance and a size.

Look for the hinge make and model if one is named, the leaf height and width, the material, the pin type, the number of hinges and their positions. The certificate may also state the screw type and whether intumescent pads are needed at the hinge. If the door has been altered since it was certificated, for example by adding a letterbox or a new closer, the original schedule may no longer describe the door in front of you.

DocumentWhat it should showWhy it matters
Door certificate or test evidenceThe tested assembly and its limitsShows whether the hinge is part of the approved specification
Hardware scheduleHinge product, size, material and numberGives the exact replacement target
Declaration of performanceDeclared fire performance and classificationConnects the marking on the hinge to the certificate
Installation instructionsFixing, adjustment and gap limitsStops a correct hinge being fitted the wrong way

If the certificate is missing, do not guess from the old hinge. The building's fire safety information or the door manufacturer may hold a copy. A qualified fire door installer can also assess the door and advise on a like-for-like replacement.

What do CE and UKCA marking mean on a hinge?

CE and UKCA marks are declarations, not quality badges. They show that the manufacturer has declared the product's performance against a standard and supplied the supporting information. For single-axis hinges, the relevant standard is BS EN 1935, which covers requirements and test methods for building hardware.

The mark may be on the hinge, the packaging or the paperwork. It should be read with the declaration of performance, which states the values that matter: fire resistance, durability, door mass and corrosion resistance. A hinge can be marked and still be wrong for your door if its declared performance does not match the certificate.

Mark or termWhat it meansWhat to check
CE markManufacturer's declaration against a harmonised standardThe declaration names the hinge and its fire performance
UKCA markUK declaration for the same kind of productThe declaration matches the product and the standard
BS EN 1935Standard for single-axis hingesThe classification includes the attributes the door needs
Third-party certificationOngoing certification of the product, such as CertifireThe certificate covers the exact product, not a similar one
Fire rated labelA claim, not a specification on its ownAsk for the declared performance and the certificate reference

Record the marking and the declaration reference when you fit the hinge. It saves an argument later and makes the next replacement easier to specify. If the mark is missing, or the declaration cannot be produced, treat the hinge as unverified. A supplier's description is not a substitute for the paperwork.

What do the grades and letters on a fire door hinge mean?

BS EN 1935 sets out a classification with several digits. The digits cover attributes such as durability, door mass, fire resistance, safety and corrosion resistance. The exact string is less useful than the declared values, because a high number in one column does not make a hinge suitable for every door.

A hinge with a high durability grade may still have the wrong fire resistance or the wrong leaf size for your door. A corrosion grade matters in a damp or coastal building, but it says nothing about fire. Read each attribute against the door's schedule, and treat a missing value as a reason to ask, not a reason to assume.

AttributeWhat it affectsWhat to record
DurabilityHow many test cycles the hinge is rated forThe grade and the test standard
Door massThe weight of leaf the hinge can carryThe rated mass against the actual leaf weight
Fire resistanceWhether the hinge is assessed for fire door useThe declared value and the certificate reference
Corrosion resistanceSuitability for damp, coastal or industrial settingsThe grade and the finish
Size and fixingLeaf dimensions, knuckle and screw patternThe measurements of the old hinge

Where the certificate names a product, the product wins over a generic grade. A higher grade is not a substitute for the tested item.

Sparrow app icon

Look after more than one home?Snap each part next to a £1 coin and Sparrow names the exact replacement, then saves it in My Home by property and room, so the next order is right first time.

Get the app

Why should you not drill new screw holes?

A fire door leaf is manufactured and tested as a solid component. A new screw hole is a small void in that component, and a row of new holes near the edge can damage the core or the fixing. It also takes the door away from the configuration that was tested, which is why the certificate matters more than the screw in your hand.

Holes close to the old ones are the worst case. The timber or core between them can crumble, and the screw has less material to grip. A longer or thicker screw is not a safe answer either, because it can break through the leaf face or bridge a layer that should stay intact.

ProblemTempting fixWhy it is a riskBetter route
Screw spins in the holeFit a longer or thicker screwCan split the core or break the faceUse the manufacturer's repair method or replace the hinge and repair the hole
New hinge has a different hole patternDrill new holes alongside the old onesChanges the tested leaf and weakens the edgeOrder the correct pattern, or have a qualified installer assess it
Hinge is slightly too smallPack it out with card or washersPacking can crush and the door can dropFit the specified size and material
Door binds after fittingPlane the door edgeRemoves material and may breach the seal or coreCheck the hinge, frame and gaps; escalate if it still binds

The same rule applies to the frame. New holes in a fire door frame can affect the frame's performance and the door's fit. If the frame side is damaged, the repair is a job for someone who knows the system, not a case of moving the hinge along.

Screw length matters as much as screw position. A screw that is too long can break through the face of the leaf or the frame, and one that is too short may not reach the fixing. Use the type and length the hinge manufacturer specifies, and check that the old screws match before you reuse them.

How to identify the hinge you need to replace

Work from the old hinge and the certificate together. The certificate tells you what is allowed; the old hinge tells you what physically fits. If the two disagree, stop and ask before ordering.

  1. Open the door and photograph the hinge in place, with the door supported.
  2. Note the number of hinges and their positions on the door edge.
  3. Measure the leaf height and width of one hinge, and its thickness.
  4. Measure the screw hole centres on the door leaf and on the frame leaf.
  5. Measure the knuckle diameter and note whether the pin is fixed or lift-off.
  6. Note the material and finish, and any maker's marks or code on the hinge.
  7. Check the certificate or hardware schedule for the specified product.
  8. Record the door reference, the location and the date before you remove anything.

A common fire door hinge is 102 mm high by 76 mm wide, often described as 4 inch by 3 inch. Do not rely on that alone. Leaf thickness, knuckle size and screw spacing vary, and a hinge that is close but not identical will fight the old holes.

If the handle is being replaced at the same time, its PZ and screw centres matter as much as the hinge pattern. The guide to uPVC door handle sizes, PZ and screw centres explains where to measure, and the same logic applies to many door hardware sets.

Which hinge types are used on fire doors?

Most fire doors use a fixed-pin butt hinge, but the door system decides. The table below describes what you are likely to see and the question to ask about each. It is not a list of approved products.

Hinge typeHow to spot itFire door note
Fixed-pin butt hingeTwo leaves, knuckle in the middle, pin cannot be lifted outThe usual choice where the certificate specifies a fixed pin
Ball-bearing butt hingeSimilar, with bearings in the knuckle and a smoother swingBearings help movement, not fire performance; check the declaration
Lift-off hingeDoor can be lifted off the frame leafCheck the certificate before using one on a fire door
Parliament hingeWide knuckle, often on older or heavy doorsOnly if the door's specification allows it
Continuous hingeA long hinge along the full door heightCommon on some commercial doors; match the system

Do not assume that a heavier hinge is better. The tested specification, not the weight of the hinge, is the target. A product that matches the certificate is worth more than one that merely feels stronger.

How many hinges should a fire door have?

The certificate or hardware schedule states the number. Most fire doors have three: top, middle and bottom. Taller or heavier leaves may have four. The positions matter as well, because they spread the load and keep the door in the frame during a fire.

Do not remove a hinge because the door closes with two. A door that works on two hinges is being held by less fixing than the tested design, and the remaining screws take more load. Do not add a fourth hinge unless the specification allows it, because a new hinge means new fixings and a change to the assembly.

What to check before you order a replacement

  • Certificate reference. Confirm the door and the hinge specification before you look at products.
  • Size. Leaf height, leaf width and thickness, measured from the old hinge.
  • Hole pattern. Screw centres on both leaves, and the number of screws.
  • Pin type. Fixed or lift-off, and the knuckle diameter.
  • Fire performance. A CE or UKCA mark plus a declaration that states the fire resistance.
  • Material and finish. Steel or stainless steel as specified, with a finish that suits the building.
  • Fixings. The screw type and length stated by the manufacturer, not a general wood screw.
  • Accessories. Intumescent pads or washers if the certificate calls for them.
  • Quantity. The same number as the door has now, plus a spare only if it is the identical product.

Buy from a supplier who can give the declaration and the certificate reference. A listing that says fire door hinge without a declared performance is not enough to order from.

How to replace a fire door hinge without new holes

Fire doors are heavy and often have a closer pulling against you. Use two people, keep the door supported, and replace the hinges one at a time so the leaf stays in place. Check the certificate before you start, not after the old hinge is off.

  1. Prop the door shut or support it under the bottom edge. Do not rely on the closer.
  2. Check the new hinge against the old one: size, hole pattern, pin type and marking.
  3. Remove the screws from one hinge leaf, holding the door steady.
  4. Ease the old hinge out. If it is painted in, score the paint line first.
  5. Fit the new hinge into the same recess or onto the same face, using the existing holes.
  6. Start the screws by hand, then tighten evenly. Stop if a screw spins.
  7. Repeat for the other hinges, one at a time.
  8. Check the door swings freely, the gaps are even and the latch enters the keep.
  9. Let the closer shut the door from partly open and confirm it latches.
  10. Record the hinge product, date and certificate reference.

Do not plane the door, bend the hinge or enlarge the recess to make a hinge fit. If the new hinge does not sit flush in the old recess, it is the wrong hinge or the door has moved. Both are reasons to stop.

What if the screw holes are worn?

A worn screw hole on a fire door is a repair question, not a bigger screw question. Filling the hole with wood filler and driving the screw back in may hold for a while, but it does not restore the fixing that the door was tested with. The same goes for matchsticks, glue and oversized screws.

Ask the door manufacturer or a qualified fire door installer for the approved repair. Some systems allow a resin repair or a new fixing plate; others call for the hinge to be repositioned only within a tested range, or for the leaf to be replaced. The right answer depends on the door construction and the certificate.

If the hole is worn because the door has dropped or the closer is pulling too hard, repair the cause as well. A new hinge in a damaged hole will loosen again.

How do you check the gaps and closing after fitting?

After the hinge is fitted, close the door and look at the gap at the top, the lock side and the hinge side. A common specification for a fire door is 2 to 4 mm at the sides and top, but the door's certificate and the installer decide. A gap that is uneven or too wide can stop the seals doing their job.

Check the self-closing action. Open the door part way, let it go and watch it close and latch without a push. A hinge that is too stiff, or a door that has dropped, can stop the latch entering the keep. Check the smoke seals are not trapped or torn.

Look at the frame as well as the door. A hinge change can pull the door against the frame at the top or the bottom, even when the hinge itself is correct. If the gap closes up at one end, stop and check the hinge seating, the recess and the frame before adjusting anything else.

Some fire door hinges have no adjustment. If the door needs to move, the answer may be packing behind a hinge leaf, which changes the assembly. Treat that as a decision for the certificate and a qualified installer, not a quick fix on the day.

What are the common fire door hinge mistakes?

  • Ordering by the words fire door hinge without checking the declared performance.
  • Assuming a heavier or more expensive hinge is automatically suitable.
  • Drilling new holes because the pattern is close but not the same.
  • Replacing one hinge with a different size or pin type from the others.
  • Using longer screws to cure a spinning screw.
  • Removing a hinge because the door closes on two.
  • Forgetting to check the self-closer and the latch after fitting.
  • Leaving the certificate reference out of the job record.

How should a building record fire door hinges?

Keep one row per door, not one row per building. Record the door reference, its location, the certificate or test evidence reference, the hinge product and size, the number of hinges, the date of the last change and who fitted it. Add a photo of the hinge marking and the declaration.

That record makes the next replacement a like-for-like order instead of an investigation. It also shows whether two doors that look the same actually have the same specification. Fire doors in a building are often fitted at different times, and the hardware can differ.

For the wider habit of recording part sizes by room and property, see keeping a replacement parts record. The same fields work for a building's door schedule, with the certificate reference added.

When is a qualified installer needed?

Use a qualified fire door installer if the certificate is missing, the hinge specification is unclear, the screw holes are worn, the door or frame is damaged, or the new hinge does not match the old pattern. Also stop if the door has been altered, if the gaps cannot be made even, or if the closer will not latch the door after fitting.

A fire door is a life safety product. The cost of an installer's visit is small against a door that no longer performs as tested. The certificate and the competent person decide, not a forum post or a product description.

How can Sparrow help with the parts around a fire door?

Made by ThinkingAI Limited, Sparrow is an iPhone app that identifies worn household parts photographed next to a one pound coin. It covers door handles, euro cylinders and window hinges, but it does not certify fire door hardware and cannot tell you whether a hinge suits a fire door certificate. Use it for the parts around the door, such as the handle or cylinder size, and keep the fire door hinge decision with the certificate and a qualified installer. The guide to photographing a part for identification shows how to get a usable image.

Frequently asked questions

Can I replace a fire door hinge myself?

You can replace it like for like if you have the door's certificate, the correct certificated hinge and the existing screw holes line up. If the certificate is missing, the hinge is a different pattern, or a hole is worn, a qualified fire door installer should decide.

What marking should a fire door hinge have?

It should carry a CE or UKCA mark and a declaration of performance that states its fire resistance, usually tested to BS EN 1935. The mark alone is not enough: the declared performance has to match the door's certificate.

Can I drill new screw holes in a fire door?

No. New holes take the leaf outside its tested configuration and can damage the core. Use the existing holes, or ask the door manufacturer or a qualified installer about an approved repair.

How many hinges should a fire door have?

The door's certificate or hardware schedule states the number. Most fire doors have three, and taller or heavier doors may have four. Do not remove a hinge to save time.

Are all ball bearing hinges fire rated?

No. Ball bearings reduce friction, but they do not make a hinge fire rated. The fire performance is declared separately and must match the door's certificate.

What size is a fire door hinge?

A common size is 102 mm high by 76 mm wide, but sizes vary by door system. Measure the old hinge and check the certificate rather than ordering by the common size alone.

Sparrow app icon

Look after more than one home?Snap each part next to a £1 coin and Sparrow names the exact replacement, then saves it in My Home by property and room, so the next order is right first time.

Get the app

The Sparrow team

Parts guides, Sparrow

We build Sparrow, the iPhone app that identifies worn household parts from a photo taken next to a £1 coin. Our guides cover the six parts Sparrow matches: tap cartridges, euro cylinder locks, uPVC window handles, door handles, shower door seals and window hinges. Every size in a guide is checked against the same parts catalogue the app uses.

Related guides

Save every part by property and roomGet the app

Stop guessing sizes.
Get Sparrow free on iPhone today!

Get the app